CONCRETE RINGS AS REQUIRED TO MIN. OF 4" TO MEET GRADE WITH 24" MAX. HEIGHT OF SPACER RINGS, INCLUDING MANHOLE FRAME, SEAL AND RING SEAL, MASTIC OR APPROVED EQUAL.
JOINTS TO BE CONFINED O-RING GASKET MEETING ASTM C-443
PRECAST CONCRETE SECTIONS CONFORMING TO ASTM C-478
MANHOLE FRAME AND LID TO BE NEENAH R-1670, SELF SEALING OR APPROVED EQUAL. IF IN PAVED AREA, CASTING SHALL ALSO BE NON-ROCKING.
STEP MA INDUSTRIES PSI-PF OR APPROVED EQUAL
4" FOR \( \leq 21" \) PIPE
5" FOR \( >21" \) PIPE
USE A-LOK SEAL OR APPROVED EQUAL WHERE PIPE PASSES THROUGH THE MANHOLE WALL.
TYPICAL
SANITARY SEWER AND STORM SEWER MANHOLE
GREATER THAN 6' IN DEPTH
FIGURE 8.1