Text read by the vision model; check the PDF for anything that matters.MANKHOLE FRAME AND LID TO BE NEENAH PSI-FF SELF SEALING OR APPROVED EQUAL. IF IN PAVED AREA, CASTING SHALL ALSO BE NON-ROCKING.
CRETEX INTERIOR CHIMNEY SEAL OR APPROVED EQUAL FOR ALL MANHOLES
CONCRETE RINGS AS REQUIRED TO MIN. OF 4" TO MEET GRADE WITH 2" MAX. HEIGHT OF SPACER RINGS, INCLUDING MANKHOLE FRAME. SEAL WITH A-LOK SEAL MASTIC OR APPROVED EQUAL.
FLAT TOP
STEP
MA INDUSTRIES PSI-FF APPROVED EQUAL
STEPS ARE NOT REQUIRED IN STORM SEWER MANKHOLE, LESS THAN 3 FEET DEEP.
JOINTS TO BE CONFINED O-RING GASKET MEETING ASTM C-443
4" FOR ≤ 21" PIPE
5" FOR >21" PIPE
PRECAST CONCRETE SECTIONS CONFORMING TO ASTM C-478
USE A-LOK SEAL OR APPROVED EQUAL WHERE PIPE PASSES THROUGH THE MANKHOLE WALL.
TYPICAL
SANITARY SEWER AND STORM SEWER MANKHOLE
6' OR LESS IN DEPTH
FIGURE 8.2