Discussion and Consideration of Change Order #2 – Tricon Construction – Tiffin Water Treatment Facility Upgrade Project – Motion to Approve — K.4

Open the PDF Searchable (OCR) PDF

Page 17 of 63

Text from the PDF text layer; check the PDF for anything that matters.
XXft Transformer Pad 10' 7' Front Bollards: typ. of 2 A Transformer Pad Details: Pad Size: 7' x 8' x 6" Alliant requires 3' on back/sides of pad and 10' in front Per plans there is 10' of space between New fence and new concrete paving Alliant is requesting protective measures for the transformer now that it's inside the fencing and adjacent to the concrete paving, such as bollards or other.