Tom & Clint, Per this exchange, we agree to issue a credit of $2,700.00. From: Tom Shedek <[email protected]> Sent: Wednesday, February 25, 2026 1:15 PM To: Gary Ganoe <[email protected]> Subject: FW: Tiffin WTP Low Lift Pumps - 0915659 Gary, Clint’s response is below. Let me know if you agree with his math and are in agreement with his deduct. Tom Tom Shedek, PMP | Project Manager TRICON CONSTRUCTION GROUP C: 913.238.6689 [email protected] From: Clint Wienen <[email protected]> Sent: Wednesday, February 25, 2026 12:40 PM To: Tom Shedek <[email protected]> Subject: RE: Tiffin WTP Low Lift Pumps - 0915659 Tom, I am in general agreement with Gary’s logic, but I don’t agree with the math behind it. SDs indicates 7.6-hp at the duty point. Test results indicate 8.1-hp at the duty point. Therefore di2erence = 0.5-hp • 0.5 hp x 760 watts/hp divided by 0.917 motor e2iciency = 414 watts/hr • A pump will need to run approximately 15 hrs/day each day to meet demand • Most utilities are charging $0.16-0.20 per kwh. I assume they get a discounted rate b/c of there usage so I would assume they pay around $0.12 per kwh. 414/1000 kw x 5,475hrs x $0.12 kwh ~ $270 per year $270 x 10 years = $2,700 2