Text from the PDF text layer; check the PDF for anything that matters.City of Tiffin Proposed Fire Code 10/15/2021
canopy is combustible or non-combustible. Exception: If the code does not require a
building to have a fire sprinkler system, section 903.8 does not apply.
Section 904.12.6 Add a new section to read as follows: Ventilation Operation. The
ventilation system shall shut down the make-up air to the hood and continue to exhaust
upon activation of the hood fire extinguishing system.
Exception:
1. Section 904.12.6.6 may be revoked if the fire extinguishing agent will not perform
to specifications due to exhausting requirements.
Section 905.1.1 Add a new section to read as follows: Class III standpipe systems.
Delete all references to class II standpipe systems and replace with class III standpipe
systems.
Section 905.3.9 Add a new section to read as follows: Additional Standpipe Systems.
Additional standpipe systems may be added to new buildings or structures as deemed
necessary by the Code Official.
Section 905.4 Requirement #1 Delete the section and replace with: In every required
interior exit stairway, a hose connection shall be provided for each story above and
below grade plane. Hose connections shall be located at the intermediate landing
between stories, unless otherwise approved by the fire code official.
Section 906.1 Delete exceptions 1 & 2 without substitution. (These exceptions would
allow for fewer fire extinguishers in apartment buildings and schools under some
circumstances.)
Section 906.3 Add a sentence to the end of the section to read as follows: The minimum
size and rating of any required portable fire extinguisher for Class A, Class B, or Class
C hazard shall be 5 lb. 2-A, 10-B, C.
Section 907.1.4 Add a new section to read as follows: Fire alarm control panels and
Fire alarm annunciator panels. Installation of fire alarm control panels and fire alarm
annunciator panels shall be installed in accordance with section 907.1.4.1 through
907.1.4.5.
Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel Height.
Installation of fire alarm panels shall not exceed 6 feet in height measured from the floor
to the top of the panel. Exception: Panel height may be altered by the code official.
Section 907.1.4.2 Add a new section to read as follows: Number of Fire Alarm Control
Panels in Buildings. Only one listed fire alarm control panel shall be allowed per
building and shall lock in the alarm until the system is reset and shall not be canceled by
the operation of an audible - alarm silencing switch. This control panel shall only receive
alarm signals from fire protection equipment.
Section 907.1.4.3 Add a new section to read as follows: Combination Fire/Security
Alarm System Panels. A listed combination fire/security alarm system panel that meets
all the requirements of this code and amendments may be permitted by approval of the
7