contract agreement
Item D - Tiffin Proposed IFC Amendment - Draft
Page 8 of 10
Text from the PDF text layer; check the PDF for anything that matters.City of Tiffin Proposed Fire Code 10/15/2021
fire code official. The fire/security panel shall be capable of providing a signal that can
differentiate between the fire and security alarm.
Section 907.1.4.4 Add a new section to read as follows: Password/PIN Protection
Prohibited. Fire alarm control panels and/or fire alarm annunciator panels that require a
password/PIN to silence an alarm/supervisory/trouble signal and/or to reset an
alarm/supervisory/trouble signal shall be prohibited.
Section 907.1.4.5 Add a new section to read as follows: Fire Alarm Annunciator
Panels. The fire code official can require addition fire alarm annunciator panels based
on the size of building and access to the building, these panels shall meet the
requirements of 907.1.4 and 907.2.
Section 907.2 Delete the section and replace with: Where required-new buildings and
structures. An approved and addressable manual, automatic or manual and automatic
fire alarm system installed in accordance with the provisions of this code and NFPA 72
shall be provided in new buildings and structures in accordance with Sections 907.2.1
through 907.2.23 and provide occupant notification in accordance with 907.5 unless
other requirements are provided by another section of this code. A minimum of one
manual fire alarm box shall be provided in an approved location to initiate a fire alarm
signal for fire alarm system employing automatic fire detectors or water-flow devices.
Where other sections of this code allow elimination of fire alarm boxes due to sprinklers
a single fire alarm box shall be installed in a location approved by the fire code official.
Exceptions:
1. The manual fire alarm box is not required for fire alarm systems dedicated to
elevator recall control and supervisory service.
2. Where the manual fire alarm box is required for Group R-2 occupancies as a
means for fire watch personnel to initiate an alarm during a sprinkler system
impairment event, the manual fire alarm box shall not be located in an area that
is accessible to the public.
3. Multi-tenant buildings required to have a manual/automatic fire alarm system
shall install one manual pull station per tenant space.
Section 907.2.1.3 Add a new section to read as follows: Group A Occupancies. In
Group A occupancies the activation of the fire alarm or fire sprinkler system shall
automatically cause all conflicting or confusing sounds and/or visual distractions to stop
and initiate illumination of all the means of exit egress components.
Section 907.2.9 Delete the sentence and replace with: Group R-2. Fire alarm systems
and smoke alarms shall be installed in Group R-2 occupancies as required in Sections
207.2.9.1 through 907.2.9.4.
Section 907.2.9.4 Add a new section to read as follows: Apartment common areas. An
automatic smoke detection system shall be installed throughout all interior corridors and
at the top of stairway enclosures serving sleeping units that activates the occupant
notification system in accordance with Section 907.5.
8