Section 903.3.5.3 Add a new section to read as follows: Water supply safety margin:
The fire sprinkler system hydraulically calculated demand per NFPA 13 or NFPA 13R
including required hose stream allowances, and domestic water demand if required by
section 903.3.5.2 must be a minimum 10%, but not less than 5 psi below the water
supply flow test curve. The flow test must have been conducted within 90 days of fire
sprinkler plan submittal to the city. The base of riser psi at the time of acceptance test
shall also be 10% but not less than 5 psi above the most demanded hydraulically
calculated pressure.
Section 903.4.2 Delete the section and replace with: Alarms. An approved
weatherproof horn/strobe device shall be mounted directly above the fire department
connection between seven (7) and ten (10) feet in height above grade. The water-flow
alarm device shall be activated by water flow equivalent to the flow of a single sprinkler
of the smallest orifice size installed in the system. Approved and supervised audible
visual notification appliances shall be installed throughout each level of the interior of
the building as required by the fire code official and NFPA 72. Where a fire alarm
system is installed, actuation of the automatic sprinkler system shall actuate the building
fire alarm system.
Section 903.5 Add the following to the end of the section: Where a forward flow test is
required as part of acceptance testing for a fire sprinkler system, a valve meeting the
requirements of an inspector’s test valve is required at the most remote location in each
fire sprinkler system or tenant/floor control valve space near a high point in the system
to allow air to be removed from that portion of the system. Where the forward flow test
is not required, or after system approval by the fire code official, one of the following
methods shall be employed at each such location to allow for removal air from the
system after maintenance work is done on the system but is not required to be used for
annual or periodic testing:
1) Manual valve, minimum 1/2 in. (15mm) size
2) Automatic air vent
3) Remote inspector’s test valve
4) Other approved means
Section 903.7 Add a new section to read as follows: Zones. Automatic sprinkler system
zones shall not exceed the area permitted by NFPA 13 or NFPA 13R and shall provide
a sprinkler control valve and water flow device for each normally occupied floor or
normally occupied space in a multi-tenant building. Except by approval of the fire code
official, all control valves shall be mounted in a readily accessible location in the
sprinkler riser room or in the stairwell of a multi-story building provided with standpipes.
Section 903.8 Add a new section to read as follows: Fire sprinkler for exterior
projections. An exterior projection as outlined in NFPA 13 attached to a building shall
be required to have fire sprinklers installed underneath for protection throughout if the
exterior projection extends more than 4 feet from the building and is 12 feet or less in
height from the ground regardless of whether the exterior projection is combustible or
noncombustible. Canopies that are attached to or within ten (10) feet of the building
and have vehicle access under them with openings into the building shall be required to
have fire sprinklers coverage installed under the canopy regardless of whether the
6