contract agreement
Item D - Tiffin Proposed IFC Amendment - Draft
Page 5 of 10
Text from the PDF text layer; check the PDF for anything that matters.City of Tiffin Proposed Fire Code 10/15/2021
is installed at a minimum 8-inch height between the fryer and surface flames to the
adjacent appliance, the requirement for a 16-inch space shall not apply.
Section 803.16 Add a new section to read as follows: Maintenance. The interior finish
of buildings shall be maintained in accordance with the conditions of original approval.
Any change to the interior finish that is regulated by the provisions of this code or the
building code shall be made in accordance with all applicable requirements.
Section 806.1 Add a sentence to the end of the section to read as follows: Natural or
resin-bearing cut trees and natural decorative vegetation used in buildings open to the
general public shall be properly treated with an approved flame retardant.
Section 807.5.2.1 Delete exception 2.
Section 807.5.5.1 Delete exception 2.
Section 901.2 (a) Add a new section to read as follows: Water-based fire protection
systems. Working plans submitted to the fire department for water-based fire protection
systems shall be stamped and approved by a qualified person to be in compliance with
applicable NFPA standards and the Tiffin Fire Code. Any changes to the working plans
shall be approved by a qualified person. A qualified person shall have a minimum
National Institute for Certification in Engineering Technologies [NICET] Level III
certification for Automatic Sprinkler System Layout OR be a licensed engineer with
experience in life safety system design. Other qualifications may be approved by the
code official.
Section 901.2 (b) Add a new section to read as follows: Fire alarm systems. Working
plans submitted to the fire department by a qualified person for fire alarm systems shall
be stamped and approved by a qualified person to be in compliance with applicable
NFPA standards and the Tiffin Fire Code. Any changes to the working plans shall be
approved by a qualified person. A qualified person shall have a minimum National
Institute for Certification in Engineering Technologies [NICET] Level III certification for
Fire Alarm Systems OR be a licensed engineer with experience in life safety system
design. Other qualifications may be approved by the code official.
Section 901.6.3.2 Add a new section to read as follows: Inspection Record
Submission. Contractors who perform installation, inspection, testing and/or
maintenance services on fire and life safety systems are required to electronically
submit all installation and compliant & non-compliant inspection reports to the Fire Code
Official via a method approved by the Fire Code Official within 30 calendar days of the
installation/inspection date. Reports submitted after 30 calendar days may incur late
fees.
Section 901.7 Add a sentence to the end of the section to read as follows: A person
assigned to fire watch must walk through the building at least once every 30 minutes
checking for fire or smoke. A fire watch must be continued until the fire alarm system
and/or fire protection system has been restored to normal operating condition or the
building has been evacuated. A competent adult familiar with the building must conduct
the fire watch, and if a fire is discovered shall call 911 and immediately evacuate the
building.