G-2, H-4 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 4 of 12
Text from the PDF text layer; check the PDF for anything that matters.Section 506.1 Insert a sentence to the beginning of the section to read as
follows: An approved key box shall be installed in an approved location on all
new construction. Add the following to the end of the section: Exception:
Group R-3 occupancies and unsecured R-2 occupancies.
Section 507.3 Delete the section and replace with: Fire flow. Fire flow
requirements for buildings or portions of buildings shall be determined by (an
approved method) "Appendix B" of this code.
Section 507.5.1 Delete exceptions 1 & 2. (Which increase the distance allowed
to a fire hydrant for sprinklered buildings, single family homes, and structures
accessory to single family homes.)
Section 507.5.1.1 Delete section and add a new section to read as follows: Fire
Sprinkler System & Standpipe System Support. A fire hydrant shall be
located no more than 100 feet from a fire sprinkler or standpipe system
connection on a hard surface, easily accessible by fire apparatus and meeting
the approval of the Code Official.
Section 507.5.7 Add a new section to read as follows: Fire hydrant threads.
All new hydrants within the city limits of Tiffin shall have National Standard
Threads (NST) on the 2 1/2-inch connections and the 4 ½-inch connection will
have a Storz connection.
Section 510.1 Delete exceptions 1 & 2. (Which would allow for a hard-wired
system in lieu of the required radio coverage or no coverage at all within a new
building or structure.)
Section 604.10 Delete the section and replace with: Portable, electric space
heaters. (Where not prohibited by other sections of this code,) Portable electric
space heaters shall (be permitted to be used in all occupancies in accordance
with) comply with Sections 604.10.1 through 604.10.6.
Section 604.10.6 Add a new section to read as follows: Fully enclosed.
Portable, electric space heaters shall be fully enclosed space heaters that by
design have no external surfaces that reach temperatures capable of igniting
materials placed against the surface.
Section 606.7. Add a sentence to the end of the section to read as follows: The
required elevator keys shall be secured in an approved elevator key box in a
location approved by the fire code official.
Section 607.4 Delete the last sentence and replace with: Movement of new and
existing cooking appliances with casters shall be limited by an approved
restraining device and flexible gas connector installed in accordance with the
connector and appliance manufacturer's instructions.
Section 607.5 Add a new section to read as follows: Required separation. All
deep-fat fryers shall be installed with at least 16-inches space between the
fryer and surface flames from adjacent cooking equipment. Where a steel or
tempered glass baffle plate is installed at a minimum 8-inch height between the