G-2, H-4 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 3 of 12
Text from the PDF text layer; check the PDF for anything that matters.implement the appropriate emergency plan and procedures. Exception: When
the emergency evacuation plan, as approved by the fire code official, does not
require the immediate total evacuation of the building.
Section 501.3 Delete the section and replace with: Construction Documents.
Construction Documents for proposed fire apparatus access, location of fire
lanes, security gates across fire apparatus access roads and construction
documents and hydraulic calculations for fire hydrant systems shall be
submitted to the (fire department) Fire Code Official for review and approval
prior to construction.
Section 505.1 Delete the section and replace with: Address Identification.
Approved numbers or addresses shall be placed on all new and existing
buildings in such a position as to be plainly visible and legible from the street
or road fronting the property. Address identification characters shall contrast
with their background. Address numbers and exterior suite numbers shall be
in Arabic numerals or alphabetical letters not less than 4-inches (102 mm) in
height with a minimum stroke width of ½-inch (12.7 mm). Numbers shall not
be spelled out. Where required by the fire code official, address identification
shall be provided in additional approved locations to facilitate emergency
response. Where access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other sign or means shall
be used to identify the structure. Exterior address location for commercial
buildings shall be determined by the Code Official. Address identification shall
be maintained.
Exceptions:
1. Monument signs shall have the address installed a minimum of 36 inches
from the ground.
2. Addresses located 100 to 199 feet from the street shall have a minimum
of 6 inches in height with a minimum stroke width of ½-inch. Addresses
located 200 to 299 feet from the street shall have a minimum of 8 inches
in height with a minimum stroke width of 1 inch. For each additional 100
feet from the street, the number shall increase by an additional 2-inches
in height with the stroke increased proportionally. Measurements to
determine the minimum number or letter size shall be measured from the
approved address location to the center line of the street for which the
premise is addressed. Minimum height and minimum stroke may be
increased by the Code Official.
3. Interior suite numbers shall be a minimum of 3-inches in height.
Section 505.3 Add a new section to read as follows: Addresses for Buildings
under Construction. All new commercial and residential buildings under
construction shall have addresses posted as to be plainly visible from the
street. Additional address signage may be required at the discretion of the Code
Official.