G-2, H-4 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 5 of 12
Text from the PDF text layer; check the PDF for anything that matters.fryer and surface flames to the adjacent appliance, the requirement for a 16-
inch space shall not apply.
Section 803.16 Add a new section to read as follows: Maintenance. The
interior finish of buildings shall be maintained in accordance with the
conditions of original approval. Any change to the interior finish that is
regulated by the provisions of this code or the building code shall be made in
accordance with all applicable requirements.
Section 806.1 Add a sentence to the end of the section to read as follows:
Natural or resin-bearing cut trees and natural decorative vegetation used in
buildings open to the general public shall be properly treated with an approved
flame retardant.
Section 807.5.2.1 Delete exception 2.
Section 807.5.5.1 Delete exception 2.
Section 901.2 (a) Add a new section to read as follows: Water-based fire
protection systems. Working plans submitted to the fire department for
water-based fire protection systems shall be stamped and approved by a
qualified person to be in compliance with applicable NFPA standards and the
Tiffin Fire Code. Any changes to the working plans shall be approved by a
qualified person. A qualified person shall have a minimum National Institute
for Certification in Engineering Technologies [NICET] Level III certification for
Automatic Sprinkler System Layout OR be a licensed engineer with experience
in life safety system design. Other qualifications may be approved by the code
official.
Section 901.2 (b) Add a new section to read as follows: Fire alarm systems.
Working plans submitted to the fire department by a qualified person for fire
alarm systems shall be stamped and approved by a qualified person to be in
compliance with applicable NFPA standards and the Tiffin Fire Code. Any
changes to the working plans shall be approved by a qualified person. A
qualified person shall have a minimum National Institute for Certification in
Engineering Technologies [NICET] Level III certification for Fire Alarm Systems
OR be a licensed engineer with experience in life safety system design. Other
qualifications may be approved by the code official.
Section 901.6.3.2 Add a new section to read as follows: Inspection Record
Submission. Contractors who perform installation, inspection, testing and/or
maintenance services on fire and life safety systems are required to
electronically submit all installation and compliant and non-compliant
inspection reports to the Fire Code Official via a method approved by the Fire
Code Official within 30 calendar days of the installation/inspection date.
Reports submitted after 30 calendar days may incur late fees.
Section 901.7 Add a sentence to the end of the section to read as follows: A
person assigned to fire watch must walk through the building at least once
every 30 minutes checking for fire or smoke. A fire watch must be continued
until the fire alarm system and/or fire protection system has been restored to
normal operating condition or the building has been evacuated. A competent