staff report memo · M-10
M-10 - Public Protection Classification Report - ISO Rating
Page 8 of 24
Text from the PDF text layer; check the PDF for anything that matters.PPC Review
ISO concluded its review of the fire suppression features being provided for Tiffin FPSA. The
resulting community classification is Class 04/4Y.
If the classification is a single class, the classification applies to properties with a Needed Fire
Flow of 3,500 gpm or less in the community. If the classification is a split class (e.g., 6/XX):
The first class (e.g., “6” in a 6/XX) applies to properties within 5 road miles of a
recognized fire station and within 1,000 feet of a fire hydrant or alternate water supply.
The second class (XX or XY) applies to properties beyond 1,000 feet of a fire hydrant
but within 5 road miles of a recognized fire station.
Alternative Water Supply: The first class (e.g., “6” in a 6/10) applies to properties within
5 road miles of a recognized fire station with no hydrant distance requirement.
Class 10 applies to properties over 5 road miles of a recognized fire station.
Class 10W applies to properties within 5 to 7 road miles of a recognized fire station with
a recognized water supply within 1,000 feet.
Specific properties with a Needed Fire Flow in excess of 3,500 gpm are evaluated
separately and assigned an individual classification.
Earned Credit
FSRS Feature Credit Available
Emergency Communications
414. Credit for Emergency Reporting 3.00 3
422. Credit for Telecommunicators 2.38 4
432. Credit for Dispatch Circuits 3.00 3
440. Credit for Emergency Communications 8.38 10
Fire Department
513. Credit for Engine Companies 5.14 6
523. Credit for Reserve Pumpers 0.00 0.50
532. Credit for Pump Capacity 3.00 3
549. Credit for Ladder Service 4.00 4
553. Credit for Reserve Ladder and Service Trucks 0.00 0.50
561. Credit for Deployment Analysis 8.70 10
571. Credit for Company Personnel 4.01 15
581. Credit for Training 2.32 9
730. Credit for Operational Considerations 2.00 2
590. Credit for Fire Department 29.17 50
Water Supply
616. Credit for Supply System 23.24 30
621. Credit for Hydrants 2.96 3
631. Credit for Inspection and Flow Testing 2.40 7
640. Credit for Water Supply 28.60 40
Divergence -2.63 --
1050. Community Risk Reduction 4.56 5.50
Total Credit 68.08 105.50
PPC is a registered trademark of Insurance Services Office, Inc.