Text from the PDF text layer; check the PDF for anything that matters.deleted new amendment #4 that was added to the 24 IFC; One-story buildings
not exceeding 12,000 square feet with no below-ground area(s).
CHAPTER 6 – BUILDING SERVICES AND SYSTEMS
SECTION 604
ELEVATOR OPERATION, MAINTENANCE AND FIRE SERVICE KEYS
Section 604.6.1 Delete section and replace with: Elevator key location. Keys for
the elevator car doors and fire-fighter service keys shall be kept in an approved
elevator key box in an approved location by the Fire Code Official for immediate
use by the fire department.
Section 604.8 Add a new section to read as follows: Elevator equipment
signage. New and existing buildings with an elevator shall have an approved,
visible sign located next to the elevator key box stating the location of the
elevator equipment room and elevator power shut-off.
Section 604.9 Add a new section to read as follows: Elevator monitoring service
or company shall provide emergency contact information to the fire code official
upon request.
SECTION 606
COMMERCIAL COOKING EQUIPMENT AND SYSTEMS
Section 606.4 Delete the last sentence and replace with: Movement of new and
existing cooking appliances with caster(s) under a Type I hood shall be limited
by an approved floor mounted restraining device installed in accordance with
the connector and appliance manufacturer’s instructions.
Section 606.5 Add a new section to read as follows: Required separation. All
deep-fat fryers shall be installed with at least 16- inch space between the fryer
and surface flames from adjacent cooking equipment. Where a steel or
tempered glass baffle plate is installed at a minimum 8-inch height between the
fryer and surface flames to the adjacent appliance, the requirement for a 16-
inch space shall not apply.
Section 606.6 Add a new section to read as follows: Kitchen Hood Exhaust Fan
Requirement. New and existing Type I hood kitchen hood exhaust/up blast
fans shall be installed with listed hinges, weatherproof electrical cable, a hold
open retainer for servicing and cleaning and grease containment.
CHAPTER 8 – INTERIOR FINISH, DECORATIVE MATERIALS AND
FURNISHINGS
SECTION 803
INTERIOR WALL AND CEILING FINISH IN EXISTING BUILDINGS
Section 803.16 Add a new section to read as follows: Maintenance. The interior
finish of buildings shall be maintained in accordance with the conditions of