ordinance · G-1,H-1
G-1, H-1 - Ordinance 2025-519 - 2024 International Fire Code with Amendents
Page 5 of 19
Text from the PDF text layer; check the PDF for anything that matters. SECTION 507
FIRE PROTECTION WATER SUPPLIES
Sections 507.2.1 Add to end of section to read as follows: Private fire service
mains shall be appropriately sized and installed to provide the required fire flow
and shall be a minimum of 8” in diameter.
Section 507.3 Delete the section and replace it with: Fire flow. Fire flow
requirements for buildings or portions of buildings shall be determined by
“Appendix B” of this code.
Section 507.5.1 Delete exceptions 1 & 2.
Section 507.5.1.1 Delete section and replace with: Fire Sprinkler System &
Standpipe System Support. A fire hydrant shall be located no more than 100
feet from a fire sprinkler or standpipe system connection on a hard surface,
located on the same side of the fire department access road, easily accessible
by fire apparatus and meeting the approval of the Fire Code Official.
Exception: The location of the fire hydrant may be modified by approval of the
Fire Code Official.
(Change: Added and Modified exception)
Section 507.5.7 Add a new section to read as follows: Fire Hydrant Installation
Section 507.5.7.1 Add a new section to read as follows: Fire hydrant outlet
direction: All fire hydrants shall be positioned so that the four and one-half (4
1/2) inch connection is facing the street or driveway accessible to fire
department apparatus.
Section 507.5.7.2 Fire hydrants threads: All new fire hydrants within the limits
of the city of Tiffin have National Standard Threads (NST) on the two and one-
half (2 1/2) inch connections and the four and one-half (4 1/2) inch connection
will have a Storz connection.
Section 507.5.7.3 Flow: The minimum flow requirements for a water main
serving a fire hydrant is the rate of water flow, at a residual pressure of twenty
pounds per square inch (20psi) and for a specified duration, as specified in
appendix B of this code and be a minimum of 8” in diameter.
Section 507.5.7.4 Add a new section to read as follows: Fire hydrant height:
Fire hydrants shall be installed a minimum of sixteen (16) inches from the
nominal ground level to the center of the lowest water outlet.
SECTION 510
EMERGENCY RESPONDER COMMUNICATIONS ENHANCEMENT SYSTEMS
Section 510.1 Delete exceptions 1 & 4.
(Change: Added back previously deleted #2; Where it is determined by the fire
code official that the communications coverage system is not needed and