Text from the PDF text layer; check the PDF for anything that matters. C. New or replacement water supply systems shall be designed to minimize or
eliminate infiltration of floodwaters into the system. Water supply treatment facilities
other than on-site systems shall be provided with a level of protection equal to or greater
than one foot above the 100-year flood elevation.
D. Utilities such as gas or electrical systems shall be located and constructed to
minimize or eliminate flood damage to the system and the risk associated with such flood
damaged or impaired systems.
7. Flammable or Explosive Materials. Storage of equipment and materials that are
flammable, explosive, or injurious to human, animal or plant life is prohibited unless elevated a
minimum of one foot above the 100-year flood level. Other material and equipment must either
be similarly elevated or: (i) not subject to major flood damage and anchored to prevent
movement due to floodwaters; or (ii) readily removable from the area within the time available
after flood warning.
8. Levees and Floodwalls. Flood control structural works such as levees, floodwalls, etc.
shall provide, at a minimum, protection from a 100-year flood with a minimum of three feet of
design freeboard and shall provide for adequate interior drainage. In addition, structural flood
control works shall be approved by the Department of Natural Resources.
9. Watercourse Alterations. Watercourse alterations or relocations must be designed to
maintain the flood carrying capacity within the altered or relocated portion. In addition, such
alterations or relocations must be approved by the Department of Natural Resources.
10. Subdivisions. Subdivisions (including factory-built home parks and subdivisions) shall
be consistent with the need to minimize flood damages and shall have adequate drainage provided
to reduce exposure to flood damage. Development associated with subdivision proposals
(including the installation of public utilities) shall meet the applicable performance standards of
this chapter. Subdivision proposals intended for residential use shall provide all lots with a means
of access which will be passable by wheeled vehicles during the 100-year flood. Proposals for
subdivisions greater than five acres or 50 lots (whichever is less) shall include 100-year flood
elevation data for those areas located within the area of significant flood hazard.
11. Accessory Structures.
A. Detached garages, sheds, and similar structures accessory to a residential use are
exempt from the 100-year flood elevation requirements where the following criteria are
satisfied:
(1) The structure shall not be used for human habitation.
(2) The structure shall be designed to have low flood damage potential.
(3) The structure shall be constructed and placed on the building site so as to
offer minimum resistance to the flow of floodwaters.
(4) The structure shall be firmly anchored to prevent flotation which may
result in damage to other structures.
(5) The structure’s service facilities such as electrical and heating equipment
shall be elevated or flood-proofed to at least one (1) foot above the 100-year
flood level.
B. Exemption from the 100-year flood elevation requirements for such a structure
may result in increased premium rates for flood insurance coverage of the structure and
its contents.