Text from the PDF text layer; check the PDF for anything that matters.certify that the flood proofing methods used are adequate to withstand the flood depths, pressures,
velocities, impact and uplift forces and other factors associated with the 100-year flood; and that
the structure, below the 100-year flood level, is watertight with walls substantially impermeable
to the passage of water. A record of the certification indicating the specific elevation (in relation
to National Geodetic Vertical Datum) to which any structures are flood-proofed shall be
maintained by the Administrator.
4. All New and Substantially Improved Structures.
A. Fully enclosed areas below the “lowest floor” (not including basements) that are
subject to flooding shall be designed to automatically equalize hydrostatic flood forces on
exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this
requirement must either be certified by a registered professional engineer or meet or
exceed the following minimum criteria:
(1) A minimum of two openings having a total net area of not less than one
square inch for every square foot of enclosed area subject to flooding shall be
provided.
(2) The bottom of all openings shall be no higher than one foot above grade.
(3) Openings may be equipped with screens, louvers, valves, or other
coverings or devices provided that they permit the automatic entry and exit of
floodwaters.
Such areas shall be used solely for parking of vehicles, building access, and low damage
potential storage.
B. New and substantially improved structures must be designed (or modified) and
adequately anchored to prevent flotation, collapse, or lateral movement of the structure
resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy.
C. New and substantially improved structures must be constructed with electrical,
heating, ventilation, plumbing, and air conditioning equipment and other service facilities
that are designed and/or located so as to prevent water from entering or accumulating
within the components during conditions of flooding.
5. Factory-Built Homes.
A. All factory-built homes, including those placed in existing factory-built home
parks or subdivisions, shall be elevated on a permanent foundation such that the lowest
floor of the structure is a minimum of one foot above the 100-year flood level.
B. All factory-built homes, including those placed in existing factory-built home
parks or subdivisions, shall be anchored to resist flotation, collapse, or lateral movement.
Methods of anchoring may include, but are not limited to, use of over-the-top or frame
ties to ground anchors.
6. Utility and Sanitary Systems.
A. On-site waste disposal and water supply systems shall be located or designed to
avoid impairment to the system or contamination from the system during flooding.
B. All new and replacement sanitary sewage systems shall be designed to minimize
or eliminate infiltration of floodwaters into the system as well as the discharge of effluent
into floodwaters. Wastewater treatment facilities (other than on-site systems) shall be
provided with a level of flood protection equal to or greater than one foot above the 100-
year flood elevation.