G-2, H-4 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 8 of 12
Text from the PDF text layer; check the PDF for anything that matters.Section 907.1.4.3 Add a new section to read as follows: Combination
Fire/Security Alarm System Panels. A listed combination fire/security alarm
system panel that meets all the requirements of this code and amendments
may be permitted by approval of the fire code official. The fire/security panel
shall be capable of providing a signal that can differentiate between the fire and
security alarm.
Section 907.1.4.4 Add a new section to read as follows: Password/PIN
Protection Prohibited. Fire alarm control panels and/or fire alarm
annunciator panels that require a password/PIN to silence an
alarm/supervisory/trouble signal and/or to reset an
alarm/supervisory/trouble signal shall be prohibited.
Section 907.1.4.5 Add a new section to read as follows: Fire Alarm
Annunciator Panels. The fire code official can require addition fire alarm
annunciator panels based on the size of building and access to the building,
these panels shall meet the requirements of 907.1.4 and 907.2.
Section 907.2 Delete the section and replace with: Where required-new
buildings and structures. An approved and addressable manual, automatic or
manual and automatic fire alarm system installed in accordance with the
provisions of this code and NFPA 72 shall be provided in new buildings and
structures in accordance with Sections 907.2.1 through 907.2.23 and provide
occupant notification in accordance with 907.5 unless other requirements are
provided by another section of this code. A minimum of one manual fire alarm
box shall be provided in an approved location to initiate a fire alarm signal for
fire alarm system employing automatic fire detectors or water-flow devices.
Where other sections of this code allow elimination of fire alarm boxes due to
sprinklers a single fire alarm box shall be installed in a location approved by
the fire code official.
Exceptions:
1. The manual fire alarm box is not required for fire alarm systems
dedicated to elevator recall control and supervisory service.
2. Where the manual fire alarm box is required for Group R-2 occupancies
as a means for fire watch personnel to initiate an alarm during a
sprinkler system impairment event, the manual fire alarm box shall not
be located in an area that is accessible to the public.
3. Multi-tenant buildings required to have a manual/automatic fire alarm
system shall install one manual pull station per tenant space.
Section 907.2.1.3 Add a new section to read as follows: Group A
Occupancies. In Group A occupancies the activation of the fire alarm or fire
sprinkler system shall automatically cause all conflicting or confusing sounds
and/or visual distractions to stop and initiate illumination of all the means of
exit egress components.