ordinance · G-2,H-4
G-2, H-4 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 7 of 12
Text from the PDF text layer; check the PDF for anything that matters.that are attached to or within ten (10) feet of the building and have vehicle
access under them with openings into the building shall be required to have
fire sprinklers coverage installed under the canopy regardless of whether the
canopy is combustible or non-combustible. Exception: If the code does not
require a building to have a fire sprinkler system, section 903.8 does not apply.
Section 904.12.6 Add a new section to read as follows: Ventilation Operation.
The ventilation system shall shut down the make-up air to the hood and
continue to exhaust upon activation of the hood fire extinguishing system.
Exception:
1. Section 904.12.6.6 may be revoked if the fire extinguishing agent will not
perform to specifications due to exhausting requirements.
Section 905.1.1 Add a new section to read as follows: Class III standpipe
systems. Delete all references to class II standpipe systems and replace with
class III standpipe systems.
Section 905.3.9 Add a new section to read as follows: Additional Standpipe
Systems. Additional standpipe systems may be added to new buildings or
structures as deemed necessary by the Code Official.
Section 905.4 Requirement #1 Delete the section and replace with: In every
required interior exit stairway, a hose connection shall be provided for each
story above and below grade plane. Hose connections shall be located at the
intermediate landing between stories, unless otherwise approved by the fire
code official.
Section 906.1 Delete exceptions 1 & 2 without substitution. (These exceptions
would allow for fewer fire extinguishers in apartment buildings and schools
under some circumstances.)
Section 906.3 Add a sentence to the end of the section to read as follows: The
minimum size and rating of any required portable fire extinguisher for Class A,
Class B, or Class C hazard shall be 5 lb. 2-A, 10-B, C.
Section 907.1.4 Add a new section to read as follows: Fire alarm control
panels and Fire alarm annunciator panels. Installation of fire alarm control
panels and fire alarm annunciator panels shall be installed in accordance with
section 907.1.4.1 through 907.1.4.5.
Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel
Height. Installation of fire alarm panels shall not exceed 6 feet in height
measured from the floor to the top of the panel. Exception: Panel height may be
altered by the code official.
Section 907.1.4.2 Add a new section to read as follows: Number of Fire Alarm
Control Panels in Buildings. Only one listed fire alarm control panel shall be
allowed per building and shall lock in the alarm until the system is reset and
shall not be canceled by the operation of an audible - alarm silencing switch.
This control panel shall only receive alarm signals from fire protection
equipment.