Text from the PDF text layer; check the PDF for anything that matters.CHAPTER 155 BUILDING CODES
“Zones. Automatic sprinkler system zones shall not exceed the area permitted by
NFPA 13 or NFPA 13R and shall provide a sprinkler control valve and water flow
device for each normally occupied floor or normally occupied space in a multi-tenant
building. Except by approval of the Fire Marshall, all control and drain valves shall
be located in the sprinkler riser room or in the stairwell of a multi-story building
provided with standpipes, mounted no higher than six feet from floor.”
61. Add a new Section 903.8 to read as follows:
“Fire Sprinkler for Exterior Projections. An exterior projection as outlined in NFPA
13 attached to a building shall be required to have fire sprinklers installed underneath
for protection throughout if the exterior projection extends more than four feet from
the building and is 12 feet or less in height from the ground regardless of whether the
exterior projection is combustible or noncombustible. Canopies that are attached to or
within 10 feet of the building and have vehicle access under them with openings into
the building shall be required to have fire sprinklers coverage installed under the
canopy regardless of whether the canopy is combustible or non-combustible.”
62. Add a new Section 903.9 to read as follows:
“Drains. As required by the Fire Marshall, all drain and testing piping serving
automatic sprinkler systems and standpipes shall be piped to the exterior of the
building.”
Exception: Automatic sprinkler systems protecting one- and two- family dwelling.
63. Add a new Section 904.16 to read as follows:
“System Annunciation. Commercial cooking automatic fire extinguishing systems
installed in buildings that do not have a fire alarm system, shall be connected to an
approved audible and visible emergency notification device to warn of system
discharge. The horn or strobe and signage shall be installed in a location approved by
the Fire Marshall, typically in the kitchen.”
64. Added a new Section 904.17 to read as follows:
“Ventilation Operation. The ventilation system shall shut down the make-up air to the
hood and continue to exhaust upon activation of the hood fire extinguishing system.
Exception: Section 904.17 may be revoked if the fire extinguishing agent will not
perform to specifications due to exhausting requirements.”
65. Add a new Section 905.1.1 to read as follows:
“Class III Standpipe Systems. Delete all references to class II standpipe systems and
replace with class III standpipe systems.”
66. Delete Section 905.3.4 exception without substitution.
67. Add a new Section 905.3.8 to read as follows:
“Additional Standpipe Systems. Additional standpipe systems may be added to new
buildings or structures as deemed necessary by the Fire Marshall.”
68. Amend Section 905.4 Requirement No. 1 delete the section and replace it
with:
“In every required interior exit stairway or exterior exit stairway or exterior exit
stairway, a hose connection shall be provided for each story above and below grade
CODE OF ORDINANCES, TIFFIN, IOWA