Text from the PDF text layer; check the PDF for anything that matters.CHAPTER 155 BUILDING CODES
“Required Separation. All deep-fat fryers shall be installed with at least 16-inches
space between the fryer and surface flames from adjacent cooking equipment. Where
a steel or tempered glass baffle plate is installed at a minimum eight-inch height
between the fryer and surface flames to the adjacent appliance, the requirement for a
16-inch space shall not apply.”
38. Add a new Section 606.6 to read as follows:
“Kitchen Hood Exhaust Fan Requirement. New and existing Type I hood kitchen
hood exhaust or up blast fans shall be installed with listed hinges, weatherproof
electrical cable, a hold open retainer for servicing and cleaning and grease
containment.”
39. Add a new Section 803.16 to read as follows:
“Maintenance. The interior finish of buildings shall be maintained in accordance with
the conditions of original approval. Any change to the interior finish that is regulated
by the provisions of this code, or the building code, shall be made in accordance with
all applicable requirements.”
40. Delete Section 807.5.2.1 exception 2.
41. Delete Section 807.5.5.1 exception 2.
42. Add a new Section 901.2(a) section to read as follows:
“Water-Based Fire Protection Systems. Working plans submitted to the fire
department for water-based fire protection systems shall be stamped and approved by
a qualified person to be in compliance with applicable NFPA standards and the Tiffin
Fire Code. Any changes to the working plans shall be approved by a qualified person.
A qualified person shall have a minimum National Institute for Certification in
Engineering Technologies (NICET) Level III certification for Automatic Sprinkler
System Layout or be a licensed engineer with experience in life safety system design.
Other qualifications may be approved by the Fire Marshall.”
43. Add a new Section 901.2(b) to read as follows:
“Fire Alarm Systems. Working plans submitted to the fire department by a qualified
person for fire alarm systems shall be stamped and approved by a qualified person to
be in compliance with applicable NFPA standards and the Tiffin Fire Code. Any
changes to the working plans shall be approved by a qualified person. A qualified
person shall have a minimum National Institute for Certification in Engineering
Technologies (NICET) Level III certification for Fire Alarm Systems or be a licensed
engineer with experience in life safety system design. Other qualifications may be
approved by the Fire Marshall.”
44. Amend Section 901.4.7.1 add a sentence to the end of the section to read as
follows:
“The fire pump room or automatic sprinkler riser room shall have an exterior access
door. The room shall have a hard-cleanable walking surface from the fire department
access road.”
45. Amend Section 901.4.7.3 add a sentence to the end of the section to read as
follows:
“The fire pump room or automatic sprinkler riser room shall have a supervised room
temperature sensor.”
CODE OF ORDINANCES, TIFFIN, IOWA
- 1290 -