Text from the PDF text layer; check the PDF for anything that matters.CHAPTER 147 WELL PROTECTION
TABLE A: SEPARATION DISTANCES
REQUIRED MINIMUM LATERAL DISTANCE
SOURCE OF CONTAMINATION FROM WELL AS HORIZONTAL ON THE GROUND
SURFACE, IN FEET
Deep Well1 Shallow Well1
WASTEWATER STRUCTURES:
Point of Discharge to Ground Surface
Sanitary and industrial
400 400
discharges
Water treatment plant wastes 50 50
Well house floor drains 5 5
Sewers and Drains2
0 – 25 feet: prohibited 0 – 25 feet: prohibited
25 – 75 feet if water main 25 – 75 feet if water main
Sanitary and storm sewers,
pipe pipe
drains
75 – 200 feet if sanitary 75 – 200 feet if sanitary
sewer pipe sewer main pipe
0 – 75 feet: prohibited 0 – 75 feet: prohibited
75 – 400 feet if water main 75 – 400 feet if water main
Sewer force mains pipe pipe
400 – 1,000 feet if sanitary 400 – 1,000 feet if sanitary
sewer pipe sewer main pipe
0 – 5 feet: prohibited 0 – 5 feet: prohibited
Water plant treatment process
5 – 50 feet if sanitary sewer 5 – 50 feet if sanitary
wastes that are treated onsite
pipe sewer main pipe
0 – 25 feet: prohibited 0 – 25 feet: prohibited
25 – 75 feet if water main 25 – 75 feet if water main
Water plant wastes to sanitary
pipe pipe
sewer
75 – 200 feet if sanitary 75 – 200 feet if sanitary
sewer pipe sewer main pipe
0 – 25 feet: prohibited 0 – 25 feet: prohibited
25 – 75 feet if water main 25 – 75 feet if water main
Well house floor drains to
pipe pipe
sewers
75 – 200 feet if sanitary 75 – 200 feet if sanitary
sewer pipe sewer main pipe
0 – 5 feet: prohibited 0 – 5 feet: prohibited
Well house floor drains to
5 – 50 feet if sanitary sewer 5 – 50 feet if sanitary
surface
pipe sewer main pipe
Land Disposal of Treated Wastes
Irrigation of wastewater 200 400
Land application of solid wastes3 200 400
Other
Cesspools and earth pit privies 200 400
Concrete vaults and septic tanks 100 200
Lagoons 400 1,000
Mechanical wastewater 200 400
treatment plants
Soil absorption fields 200 400