Text from the PDF text layer; check the PDF for anything that matters.Section 907.2.1.3 Add a new section to read as follows: Group A Occupancies.
In Group A occupancies, the activation of the fire alarm or fire sprinkler system,
shall automatically shut down or stop music, sound systems, conflicting or
confusing sounds and visual distractions and initiate illumination of all the
means of exit egress components.
Section 907.2.9.1 Delete exception 2 without substitution.
Section 907.2.11.2 Modify by adding a fourth location requirement as follows: 4)
Supervised smoke detectors shall be installed in all common corridors and at the
top and bottom of all stairway enclosures in Groups R-2, R-4 and I-1
occupancies. In corridors, detectors shall be located within fifteen (15) feet of the
end of the corridor and in such a way that one detector is located for each thirty
(30) feet of corridor length or spaced as allowed by the code.
Section 907.4.2 Add a sentence to the end of the section to read as follows: Where
the Fire Code Official determines that manual fire alarm boxes may be used to
cause false fire alarms, the Fire Code Official is authorized to modify the
requirements for manual fire alarm boxes.
Section 907.6.3 Delete this section and replace with: Initiating device
identification. The fire alarm system shall identify the specific initiating device
with an alphanumeric address description showing location, type of device, and
status including indication of normal, alarm, trouble, and supervisory, as
appropriate. Alphanumeric descriptions and locations shall be reported to the
Emergency Communications Center upon activation of an alarm condition as
specified by the Fire Code Official.
Exception:
1. Special initiation devices that do not support individual device
identification.
Section 907.6.4.3 Add a new section to read as follows: Zone and address location
labeling. Fire alarm and/ or annunciator panels shall have all zones and address
points plainly and permanently labeled as to their location on the outside of the
panel or on an easily readable map of the building if no display is present.
Section 907.6.6 Delete the section and replace with: Monitoring. All fire alarms
required by this chapter, the International Building Code, or the Fire Code
Official, shall be monitored by an approved UL listed Central Station service in
accordance with NFPA 72 to provide for the immediate and automatic notification
of the Emergency Communications Center. Each initiating device shall report an
address point and an alpha/numeric descriptor showing location, type of device
and status including indication of normal, alarm, trouble, and supervisory
status, as appropriate. Alpha/numeric descriptor shall be required to be reported
to the emergency communications center upon activation of alarm conditions as
specified by the Fire Code Official.
Exception: Monitoring by a supervising station is not required for:
1. Single and multiple-station smoke alarms required by Section 907.2.10.
2. Smoke detectors in Group 1-3 occupancies.