Text from the PDF text layer; check the PDF for anything that matters. 3. Automatic sprinkler systems in one and two-family dwellings
4. Fire alarm systems in one- and two-family dwellings
Section 907.7.4 Add a new section to read as follows: Device/Zone Map. An easily
readable fire alarm device and/ or zone map of the building shall be permanently
mounted in or near the fire alarm control panel and documentation cabinet
showing the location of all initiating devices when required by the Fire Code
Official.
Section 907.11 Add a new section to read as follows: Approved hold-open devices.
When installed in buildings that have a fire alarm system and/ or sprinkler
system, all approved hold-open devices shall release upon activation of a fire
alarm and/ or sprinkler water-flow activation.
Section 912.4.1 Delete the sentence and replace with: Locking fire department
connections caps. Locking fire department connections caps approved by the fire
department are required for all new construction that have a water-based fire
protective system and existing structures that have a water-based fire protective
system immediately after conducting the five-year obstruction and maintenance
testing or if one or more of the fire department caps are missing.
Section 912.8 Add a section to read as follows: Fire Department Connection
Height. The fire department connection shall be located not less than 18 inches
from the bottom of the cap(s) and not more than 3 feet from the top of the cap(s)
above the level of the adjacent grade or access level. Deviation from this height
may be granted by the Fire Code Official for just cause.
Section 912.9 Add a new section to read as follows: Size. Minimum fire
department connection size shall be 2 ½-inch National Standard Thread Siamese
connection.
Section 1008.3.3 Delete number 5 and replace with: 5. Public restrooms designed
for simultaneous use by more than one occupant.
Section 1008.3.6 Add a new section to read as follows: Additional emergency
lights: Emergency lights may be required at the discretion of the Fire Code Official
for illumination in the event of a power failure.
Section 1103.11 Add a new section to read as follows: Existing fire alarm systems
monitoring requirements. Existing fire alarms systems that are currently not
monitored by an approved UL listed Central Station shall become monitored
within 1 year from receiving notice in accordance with section 907.6.6.
Section 5003.5 Add a sentence to the end of the section to read as follows:
Signs shall also comply with the requirements of the Iowa Right to Know law.
Section 3. Repealer. All ordinances or parts of ordinances in conflict with
the provisions of this Ordinance are hereby repealed.
Section 4. Severability Clause. If any section, provision, or part of this
ordinance shall be adjudged invalid or unconstitutional, such adjudication shall
not affect the validity of the ordinance as a whole or any section, provision or
part thereof not adjudged invalid or unconstitutional.