Text from the PDF text layer; check the PDF for anything that matters.Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel Height.
Installation of fire alarm panels shall not exceed 6 feet in height measured from
the floor to the top of the panel. Exception: Panel height may be altered by the
Fire Code Official.
Section 907.1.4. 2 Add a new section to read as follows: Number of Fire Alarm
Control Panels in Buildings. Only one listed fire alarm control panel shall be
allowed per building and shall lock in the alarm until the system is reset and
shall not be canceled by the operation of an audible - alarm silencing switch. This
control panel shall only receive alarm signals from fire protection equipment.
Section 907.1.4.3 Add a new section to read as follows: Combination
Fire/Security Alarm System Panels. A listed combination fire/ security alarm
system panel that meets all the requirements of this code and amendments may
be permitted by approval of the Fire Code Official. The fire/ security panel shall
be capable of providing a signal that can differentiate between the fire and
security alarm.
Section 907.1.4.4 Add a new section to read as follows: Password/PIN Protection
Prohibited. Fire alarm control panels and/ or fire alarm annunciator panels that
require a password/PIN to silence an alarm/ supervisory /trouble signal and/ or
to reset an alarm/ supervisory/ trouble signal shall be prohibited.
Section 907.1.4.5 Add a new section to read as follows: Fire Alarm Annunciator
Panels. The Fire Code Official can require addition fire alarm annunciator panels
based on the size of building and access to the building, these panels shall meet
the requirements of 907.1.4 and 907.2.
Section 907.2 Delete the section and replace with: Where required-new buildings
and structures. An approved and addressable manual, automatic or manual and
automatic fire alarm system installed in accordance with the provisions of this
code and NFPA 72 shall be provided in new buildings and structures in
accordance with Sections 907.2.1 through 907.2.23 and provide occupant
notification in accordance with 907.5 unless other requirements are provided by
another section of this code. Not fewer than one manual fire alarm box shall be
provided in an approved location to initiate a fire alarm signal for fire alarm
system employing automatic fire detectors or water-flow devices. Where other
sections of this code allow elimination of fire alarm boxes due to sprinklers a
single fire alarm box shall be installed in a location approved by the Fire Code
Official.
Exceptions:
1. The manual fire alarm box is not required for fire alarm systems dedicated
to elevator recall control and supervisory service.
2. Where the manual fire alarm box is required for Group R-2 occupancies
as a means for fire watch personnel to initiate an alarm during a sprinkler
system impairment event, the manual fire alarm box shall not be located
in an area that is accessible to the public.
3. Multi-tenant buildings required to have a manual/automatic fire alarm
system shall install one manual pull station per tenant space.
4. Visual notification appliances are not required within self-storage units.