Text from the PDF text layer; check the PDF for anything that matters.approval of the Fire Code Official, all control and drain valves shall be located in
the sprinkler riser room or in the stairwell of a multi-story building provided with
standpipes, mounted no higher than 6 feet from floor.
Section 903.8 Add a new section to read as follows: Fire sprinkler for exterior
projections. An exterior projection as outlined in NFPA 13 attached to a building
shall be required to have fire sprinklers installed underneath for protection
throughout if the exterior projection extends more than 4 feet from the building
and is 12 feet or less in height from the ground regardless of whether the exterior
projection is combustible or noncombustible. Canopies that are attached to or
within ten (10) feet of the building and have vehicle access under them with
openings into the building shall be required to have fire sprinklers coverage
installed under the canopy regardless of whether the canopy is combustible or
non-combustible.
Section 904.13.6 Add a new section to read as follows: System Annunciation.
Commercial cooking automatic fire extinguishing systems installed in buildings
that do not have a fire alarm system, shall be connected to an approved audible
and visible emergency notification device to warn of system discharge. The
horn/strobe and signage shall be installed in a location approved by the Fire
Code Official, typically in the kitchen.
Section 904.13.7 Add a new section to read as follows: Ventilation Operation. The
ventilation system shall shut down the make-up air to the hood and continue to
exhaust upon activation of the hood fire extinguishing system. Exception: Section
904.12.6.6 may be revoked if the fire extinguishing agent will not perform to
specifications due to exhausting requirements.
Section 905.1.1 Add a new section to read as follows: Class III standpipe systems.
Delete all references to class II standpipe systems and replace with class III
standpipe systems.
Section 905.3.4 Delete the exception without substitution.
Section 905.3.9 Add a new section to read as follows: Additional Standpipe
Systems. Additional standpipe systems may be added to new buildings or
structures as deemed necessary by the Fire Code Official.
Section 905.4 Requirement # 1 Delete the section and replace it with: In every
required interior exit stairway, a hose connection shall be provided for each story
above and below grade plane. Hose connections shall be located at the
intermediate landing between stories, unless otherwise approved by the Fire Code
Official.
Section 906.1 Delete exceptions 1, 2, & 3 without substitution.
Section 906.3 Add a sentence to the end of the section to read as follows: The
minimum size and rating of any required portable fire extinguisher for Class A,
Class B, or Class C hazard shall be 5 lb. 2-A, 10-B, C.
Section 907.1.4 Add a new section to read as follows: Fire alarm control panels
and Fire alarm annunciator panels. Installation of fire alarm control panels and
fire alarm annunciator panels shall be installed in accordance with section
907.1.4.1 through 907.1.4.5.