Text from the PDF text layer; check the PDF for anything that matters. SECTION 907
FIRE ALARM AND DETECTION SYSTEMS
Section 906.3 Add a sentence to the end of the section to read as follows: The
minimum size and rating of any required portable fire extinguisher for Class A,
Class B, or Class C hazard shall be 5lb. 2-A, 10-B C.
Section 907.1.4 Add a new section to read as follows: Fire alarm control panels
and Fire alarm annunciator panels. Installation of fire alarm control panels and
fire alarm annunciator panels shall be installed in accordance with section
907.1.4.1 through 907.1.4.5.
Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel
Height: Installation of fire alarm panels shall not exceed 6 feet in height
measured from the floor to the top of the panel.
Exception: Panel height may be altered by the Fire Code Official.
Section 907.1.4.2 Add a new section to read as follows: Number of Fire Alarm
Control Panels in Buildings: Only one listed fire alarm control panel shall be
allowed per building and shall lock in the alarm until the system is reset and
shall not be canceled by the operation of an audible – alarm silencing switch.
This control panel shall only receive alarm signals from fire protection
equipment.
Section 907.1.4.3 Add a new section to read as follows: Combination
Fire/Security Alarm System Panels. A listed combination fire/security alarm
system panel that meets all the requirements of this code and amendments
may be permitted by approval of the Fire Code Official. The fire/security panel
shall be capable of providing a signal that can differentiate between the fire and
security alarm.
Section 907.1.4.4 Add a new section to read as follows: Password/PIN
Protection Prohibited: Fire alarm control panels and/or fire alarm annunciator
panels that require a password/PIN to silence an alarm/supervisory/trouble
signal and/or to reset an alarm/supervisory/trouble signal shall be prohibited.
Section 907.1.4.5 Add a new section to read as follows: Fire Alarm Annunciator
Panels: The Fire Code Official can require addition fire alarm annunciator
panels based on the size of building and access to the building, these panels
shall meet the requirements of 907.1.4 and 907.2.
Section 907.2 Delete the section and replace it with: Where required new
buildings and structures. An approved and addressable manual, automatic or
manual and automatic fire alarm system installed in accordance with the
provisions of this code and NFPA 72 shall be provided in new buildings and
structures in accordance with Sections 907.2.1 through 907.2.23 and provide
occupant notification in accordance with 907.5 unless other requirements are
provided by another section of this code. Not fewer than one manual fire alarm
box shall be provided in an approved location to initiate a fire alarm signal for