Text from the PDF text layer; check the PDF for anything that matters. SECTION 904
ALTERNATIVE AUTOMATIC FIRE EXTINGUISHING SYSTEMS
Section 904.16 Add a new section to read as follows: System Annunciation.
Commercial cooking automatic fire extinguishing systems installed in buildings
that do not have a fire alarm system, shall be connected to an approved audible
and visible emergency notification device to warn of system discharge. The
horn/strobe and signage shall be installed in a location approved by the Fire
Code Official, typically in the kitchen.
Section 904.17 Add a new section to read as follows: Ventilation Operation. The
ventilation system shall shut down the make-up air to the hood and continue
to exhaust upon activation of the hood fire extinguishing system. Exception:
Section 904.17 may be revoked if the fire extinguishing agent will not perform
to specifications due to exhausting requirements.
SECTION 905
STANDPIPE SYSTEMS
Section 905.1.1 Add a new section to read as follows: Delete all references to
class II standpipe system and replace with class III standpipe systems.
Section 905.3.4 Delete the exception without substitution.
Section 905.3.8 Add a new section to read as follows: Additional Standpipe
Systems: Additional standpipe systems may be added to new buildings or
structures as deemed necessary by the Fire Code Official.
Section 905.4 Requirement #1 Delete the section and replace it with: In every
required interior exit stairway, a hose connection shall be provided for each
story above and below grade plane. Hose connections shall be located at
intermediate landing between stories, unless otherwise approved by the Fire
Code Official.
Section 905.4 Requirement #1 Delete the section and replace it with: In every
required interior exit stairway or exterior exit stairway, a hose connection shall
be provided for each story above and below grade plane. Hose connections shall
be located at intermediate landing between stories, unless otherwise approved
by the Fire Code Official.
(Change: Added "exterior exit stairway to match new IFC language)
SECTION 906
PORTABLE FIRE EXTINGUISHERS
Section 906.1 Delete exception.
Section 906.1 Delete exceptions 1, 2 and 3.