Text from the PDF text layer; check the PDF for anything that matters. above the base flood elevation, or together with attendant utility and sanitary systems, be
floodproofed to such a level. When floodproofing is utilized, a professional engineer
registered in the State of Iowa shall certify that the floodproofing methods used are
adequate to withstand the flood depths, pressures, velocities, impact and uplift forces and
other factors associated with the base flood; and that the structure, below the base flood
elevation is watertight with walls substantially impermeable to the passage of water. A
record of the certification indicating the specific elevation (in relation to North American
Vertical Datum 1988) to which any structures are floodproofed shall be maintained by the
Floodplain Administrator.
D. All New and Substantially Improved Structures:
(1) Fully enclosed areas below the lowest floor (not including basements) that
are subject to flooding shall be designed to automatically equalize hydrostatic
flood forces on exterior walls by allowing for the entry and exit of floodwaters.
Designs for meeting this requirement must either be certified by a registered
professional engineer or meet or exceed the following minimum criteria:
a. A minimum of two openings having a total net area of not less
than one square inch for every square foot of enclosed area subject to
flooding shall be provided. (ALTERNATIVE LANGUAGE: A minimum
of two (2) openings, with positioning on at least two (2) walls, having a
total net area of not less than one square inch for every square foot of
enclosed area subject to flooding shall be provided.) [Note: The NFIP’s
Lowest Floor Guide requires that openings be located on “at least two
walls”. While FEMA does not require the ordinance to contain this
language, including it might help to ensure that the property owner will
receive a lower flood insurance premium.]
b. The bottom of all openings shall be no higher than one foot above
grade.
c. Openings may be equipped with screens, louvers, valves, or other
coverings or devices provided they permit the automatic entry and exit of
floodwaters.
Such areas shall be used solely for parking of vehicles, building access and low
damage potential storage. (OPTIONAL LANGUAGE: Where the distance
between the floor and ceiling of the fully enclosed area below the “lowest floor” is
(FIVE (5) feet or more, the applicant shall be required to sign and record with the
Johnson County Recorder a Non-Conversion Agreement that ensures the lower
enclosed area remains compliant with the criteria outlined in this subsection.)
[Note: Community may determine the height of the lower-enclosed area at which
to require the applicant to sign a Non-Conversion Agreement.]
(2) New and substantially improved structures must be designed (or modified)
and adequately anchored to prevent flotation, collapse, or lateral movement of the
structure resulting from hydrodynamic and hydrostatic loads, including the effects
of buoyancy.
(3) New and substantially improved structures shall be constructed with
electric meter, electrical service panel box, hot water heater, heating, air
conditioning, ventilation equipment (including ductwork), and other similar
machinery and equipment elevated (or in the case on non-residential structures,
cty_hr_d_160.doc - 10 - 4/15/2021