Dated November 8, 2006 2 pages Res. 2006-045

Open the PDF

Page 2 of 2

Text read by the vision model; check the PDF for anything that matters.
Addition to City of Tiffin Design Standards November 08, 2006 Water Distribution Section 7.H.5. Remove and replace with the following: Service pipe must be either seamless annealed copper, Type K conforming to ASTM B-88, or P.E. 3408 as defined in current ASTM D2239 and AWWA C901 P.E. 200 psi. rated pipe. See Figure 7.3 for typical water service installation.