Text read by the vision model; check the PDF for anything that matters.CHAPTER 6 – BUILDING SERVICES AND SYSTEMS
SECTION 604
ELEVATOR OPERATION, MAINTENANCE AND FIRE SERVICE KEYS
Section 604.6.1 Delete section and replace with: Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved elevator key box in an approved location by the Fire Code Official for immediate use by the fire department.
Section 604.8 Add a new section to read as follows: Elevator equipment signage. New and existing buildings with an elevator shall have an approved, visible sign located next to the elevator key box stating the location of the elevator equipment room and elevator power shut-off.
Section 604.9 Add a new section to read as follows: Elevator monitoring service or company shall provide emergency contact information to the fire code official upon request.
SECTION 606
COMMERCIAL COOKING EQUIPMENT AND SYSTEMS
Section 606.4 Delete the last sentence and replace with: Movement of new and existing cooking appliances with caster(s) under a Type I hood shall be limited by an approved floor mounted restraining device installed in accordance with the connector and appliance manufacturer’s instructions.
Section 606.5 Add a new section to read as follows: Required separation. All deep-fat fryers shall be installed with at least 16- inch space between the fryer and surface flames from adjacent cooking equipment. Where a steel or tempered glass baffle plate is installed at a minimum 8-inch height between the fryer and surface flames to the adjacent appliance, the requirement for a 16-inch space shall not apply.
Section 606.6 Add a new section to read as follows: Kitchen Hood Exhaust Fan Requirement. New and existing Type I hood kitchen hood exhaust/up blast fans shall be installed with listed hinges, weatherproof electrical cable, a hold open retainer for servicing and cleaning and grease containment.
CHAPTER 8 – INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
SECTION 803
INTERIOR WALL AND CEILING FINISH IN EXISTING BUILDINGS
Section 803.16 Add a new section to read as follows: Maintenance. The interior finish of buildings shall be maintained in accordance with the conditions of