ordinance

Ordinances-2025-519

Dated April 3, 2025 20 pages Ord. 2025-519, Ord. 519

Open the PDF Searchable (OCR) PDF

Page 10 of 20

Text read by the vision model; check the PDF for anything that matters.
Section 903.5.1 Add a new section to read as follows: Inspector’s test valve. An inspector’s test valve is required at the most remote location in each fire sprinkler system or tenant/floor control valve space, for use at the acceptance test and to remove air from the system after maintenance work is done on the system. Section 903.5.2 Add a new section to read as follows: Forward Flow Testing. Automatic sprinkler systems shall be provided with an external outlet to perform forward flow testing as required by NFPA 25. Control valve shall be supervised, and outlet shall be signed as testing and have male threads. Section 903.5.2 Add a new section to read as follows: Forward Flow Testing. Automatic sprinkler systems shall be provided with an external outlet to perform forward flow testing as required by NFPA 25. Control valve shall be supervised, signed as testing and have male threads. Section 903.7 Add a new section to read as follows: Zones. Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 or NFPA 13R and shall provide a sprinkler control valve and water flow device for each normally occupied floor or normally occupied space in a multi-tenant building. Except by approval of the Fire Code Official, all control and drain valves shall be located in the sprinkler riser room or in the stairwell of a multi-story building provided with standpipes, mounted no higher than 6 feet from floor. Section 903.8 Add a new section to read as follows: Fire sprinkler for exterior projections. An exterior projection as outlined in NFPA 13 attached to a building shall be required to have fire sprinklers installed underneath for protection throughout if the exterior projection extends more than 4 feet from the building and is 12 feet or less in height from the ground regardless of whether the exterior projection is combustible or noncombustible. Canopies that are attached to or within ten (10) feet of the building and have vehicle access under them with openings into the building shall be required to have fire sprinklers coverage installed under the canopy regardless of whether the canopy is combustible or non-combustible. Section 903.9 Add a new section to read as follows: Drains. As required by the Fire Code Official, all drain and testing piping serving automatic sprinkler systems and standpipes shall be piped to the exterior of the building. Exception: Automatic sprinkler systems protecting one- and two-family dwellings.

Sources

  • laserfiche: Ordinances-2025-519 (Ordinances-2025-519.pdf) — where it was found ↗ first seen Oct 12, 2026

This document's details as JSON

Data last updated October 15, 2026. Built from the archive's documents; see how the data is built.