ordinance · H-2
H-2 - Ordinance 2021-484 - Amending the 2018 International Fire Code
Page 10 of 12
Text from the PDF text layer; check the PDF for anything that matters.Section 907.7.4 Add a new section to read as follows: Device/Zone Map. An
easily readable fire alarm device and/or zone map of the building shall be
permanently mounted in or near the fire alarm control panel when required by
the fire code official.
Section 907.11 Add a new section to read as follows: Approved hold-open
devices. When installed in buildings that have a fire alarm system and/or
sprinkler system, all approved hold-open devices shall release upon activation
of a fire alarm and/or sprinkler water-flow activation.
Section 912.8 Add a new section to read as follows: Size. Minimum fire
department connection size shall be 2 ½-inch National Standard Thread unless
specifically approved by the fire code official.
Section 1008.3.3 Delete number 5 and replace with: 5. Public restrooms
designed for simultaneous use by more than one occupant. (Rather than > 300
square feet.)
Section 1008.3.6 Add a new section to read as follows: Circuit
wiring. Emergency lights shall be on the same electrical lighting circuit as the
area being served for the purpose of conducting monthly and annual testing.
Section 1013.7 Add a new section to read as follows: Circuit wring. Electrical
power for illumination of exit signs shall be from the same electrical lighting
circuit as the area being served for the purpose of conducting monthly and
annual testing.
Section 5003.3.1.4 Delete section and replace with: Responsibility for
cleanup. The person, firm or corporation responsible for an unauthorized
discharge shall institute and complete all actions necessary to remedy the
effects of such unauthorized discharge, whether sudden or gradual, without
cost to the jurisdiction. Where deemed necessary by the fire code official, fire
chief, or duly authorized fire department member, cleanup can be initiated by
the fire department or by an authorized individual or firm. Costs associated
with such cleanup shall be borne by the owner, operator, or other person
responsible for the unauthorized discharge.
Section 5003.5 Add a sentence to the end of the section to read as follows:
Signs shall also comply with the requirements of the Iowa Right to Know law.
Section 3. Repealer. All ordinances or parts of ordinances in conflict with the
provisions of this Ordinance are hereby repealed.
Section 4. Severability Clause. If any section, provision or part of this
ordinance shall be adjudged invalid or unconstitutional, such adjudication
shall not affect the validity of the ordinance as a whole or any section,
provision or part thereof not adjudged invalid or unconstitutional.
Section 5. When Effective. This ordinance shall be in effect after its final
passage, approval, and posting as provided by law.