Text from the PDF text layer; check the PDF for anything that matters.Section 901.2 (a) Add a new section to read as follows: Water-based fire
protection systems. Working plans submitted to the fire department for water-
based fire protection systems shall be stamped and approved by a qualified
person to be in compliance with applicable NFPA standards and the Tiffin Fire
Code. Any changes to the working plans shall be approved by a qualified person.
A qualified person shall have a minimum National Institute for Certification in
Engineering Technologies [NICET] Level III certification for Automatic Sprinkler
System Layout OR be a licensed engineer with experience in life safety system
design. Other qualifications may be approved by the Fire Code Official.
Section 901.2 (b) Add a new section to read as follows: Fire alarm systems.
Working plans submitted to the fire department by a qualified person for fire
alarm systems shall be stamped and approved by a qualified person to be in
compliance with applicable NFPA standards and the Tiffin Fire Code. Any
changes to the working plans shall be approved by a qualified person. A qualified
person shall have a minimum National Institute for Certification in Engineering
Technologies [NICET] Level III certification for Fire Alarm Systems OR be a
licensed engineer with experience in life safety system design. Other
qualifications may be approved by the Fire Code Official.
Section 901.4.7.1. Add a sentence to the end of the section to read as follows:
The fire pump room or automatic sprinkler riser room shall have an exterior
access door. The room shall have a hard-cleanable walking surface from the fire
department access road.
Section 901.4.7.3. Add a sentence to the end of the section to read as follows:
The fire pump room or automatic sprinkler riser room shall have a supervised
room temperature sensor.
Section 901.4.7.4. Add a sentence to the end of the section to read as follows:
Emergency lighting shall be provided in the fire pump room or automatic
sprinkler riser room
Section 901.4.7.5 Add a new section to read as follows: Additional Requirements.
The fire pump room or automatic sprinkler riser room shall be separated from
electrical room and have no electrical panels inside the rooms other than
electrical power required for the use of the fire alarm and fire protection
equipment and have a floor drain. Unless otherwise approved by the Fire Code
Official, the fire sprinkler riser room with one sprinkler riser shall have a
minimum area of sixteen (16) square feet with a minimum dimension of four (4)
feet providing at least three (3) feet clearance in front of the sprinkler, fire alarm
control panel and fire pump equipment. If additional sprinkler risers are
installed, the room size shall be increased to provide at least three (3) feet of
clearance in front of each riser.
Section 901.6.3.2 Add a new section to read as follows: Inspection Record
Submission. Contractors who perform installation, inspection, testing and/ or
maintenance services on fire and life safety systems are required to electronically
submit all installation and compliant and non-compliant inspection reports to
the Fire Code Official via a method approved by the Fire Code Official within 30