Text from the PDF text layer; check the PDF for anything that matters.Section 903.3.5 Delete the section and replace it with: Water supplies for
automatic sprinkler systems shall comply with this section and the standards
referenced in Section 903.3.1. The portable water supply shall be protected
against backflow in accordance with the requirements of this section and the
International Plumbing Code. The backflow preventor shall include a detector
(water meter) unless the fire code official approves an exception in consultation
with the water supply utility. For connections to public waterworks systems,
the water supply test used for design of fire protection systems shall be
adjusted to account for seasonal and daily pressure fluctuation based on
information from the water supply authority and as approved by the fire code
official.
Cedar Rapids already requires. Iowa City is going to require.
Section 903.3.5.1 Delete this section and replace it with: A single domestic and
automatic fire sprinkler system water supply. If the city water provider requires
a single domestic and automatic fire sprinkler system supply, then the water
supply shall be split outside of the building and shall have a shutoff provided
for the domestic service after the split outside of the building. The total
domestic demand is required to be added to the fire sprinkler demand.
Section 903.3.5.2 Delete this section.
Section 903.3.5.3 Add a new section to read as follows: Water supply safety
margin: The fire sprinkler system hydraulically calculated demand per NFPA 13
or NFPA 13R including required hose stream allowances, and domestic water
demand if required by section 903.3.5.1 must be a minimum 10%, but not less
than 5 psi below the water supply flow test curve, the flow test must have been
conducted within 90 days of fire sprinkler plan submittal to the city and third-
party reviewer (if applicable). The base of riser psi at the time of acceptance test
shall also be 10% but not less than 5 psi above the most demanding
hydraulically calculated pressure.
Section 903.4.1 Delete exception number 5 without substitution.
Section 903.4.3 Delete the section and replace it with: Alarms. An approved
weatherproof horn/strobe device shall be mounted directly above the fire
department connection between seven (7) and ten (10) feet in height above
grade. The water-flow alarm device shall be activated by water flow equivalent
to the flow of a single sprinkler of the smallest orifice size installed in the
system. Approved and supervised audible visual notification appliances shall be
installed throughout each level of the interior of the building as required by the
Fire Code Official and NFPA 72. Where a fire alarm system is installed,
actuation of the automatic sprinkler system shall actuate the building fire
alarm system.
Exception: Automatic sprinkler systems protecting one- and two-
family dwellings.
(Change: Exception added to match IFC)