Text from the PDF text layer; check the PDF for anything that matters.Section 901.4.7.4. Add a sentence to the end of the section to read as follows:
Emergency lighting shall be provided in the fire pump room or automatic
sprinkler riser room.
Section 901.4.7.5 Add a new section to read as follows: Additional
Requirements. The fire pump room or automatic sprinkler riser room shall be
separated from electrical room and have no electrical panels inside the rooms
other than electrical power required for the use of the fire alarm and fire
protection equipment and have a floor drain. Unless otherwise approved by the
Fire Code Official, the fire sprinkler riser room with one sprinkler riser shall
have a minimum area of sixteen (16) square feet with a minimum dimension of
four (4) feet providing at least three (3) feet clearance in front of the sprinkler,
fire alarm control panel and fire pump equipment. If additional sprinkler risers
are installed, the room size shall be increased to provide at least three (3) feet of
clearance in front of each riser.
Section 901.6.3.2 Add a new section to read as follows: Inspection Record
Submission. Contractors who perform installation, inspection, testing and/or
maintenance services on fire and life safety systems are required to
electronically submit all installation and compliant & non-compliant inspection
reports to the Fire Department via a method approved by the Fire Code Official
within 30 calendar days of the installation/inspection date. Reports submitted
after 30 calendar days may incur late fees.
Section 901.7 Add a sentence to the end of the section to read as follows: A
person assigned to firewatch must walk through the building at least once
every 30 minutes checking for fire or smoke. A firewatch must be continued
until the fire alarm system and/or fire protection system has been restored to
normal operating condition. A competent adult familiar with the building must
conduct the firewatch. If a fire is discovered, call 911 and immediately evacuate
the building. Exception: Firewatch may not be required by approval of the Fire
Code Official, if the building has been evacuated and secured.
(Change: Add exception that a fire watch is not required by approval
SECTION 903
AUTOMATIC SPRINKLER SYSTEMS
Section 903.3.1.1.2 Delete the section and replace with: In Group R
occupancies, sprinkler protection shall be provided in all bathrooms in NFPA
13 & NFPA 13R systems regardless of the bathroom size. The walls and
ceilings, including the walls and ceilings behind a shower enclosure or tub,
shall be noncombustible or limited-combustible materials with a 15-minute
thermal barrier rating.
Section 903.3.1.1.4 Add a new section to read as follows: Strip malls, multi-
occupant/tenant or shell buildings: The minimum sprinkler design density for
all new multi-occupant/tenant or shell buildings shall be Ordinary Hazard
(Group 2) as outlined in NFPA 13.
(Change: Provide a minimum design standard for these types of occupancies)