Text from the PDF text layer; check the PDF for anything that matters.a water-based fire protective system and existing structures that have a water-
based fire protective system immediately after conducting the five-year
obstruction and maintenance testing or if one or more of the fire department
caps are missing.
Section 912.8 Add a section to read as follows: Fire Department Connection
Height. The fire department connection shall be located not less than 18 inches
from the bottom of the cap(s) and not more than 3 feet from the top of the
cap(s) above the level of the adjacent grade or access level. Deviation from this
height may be granted by the Fire Code Official for just cause.
Section 912.9 Add a section to read as follows: Size. Minimum fire department
connection size shall be 2 ½” National Standard Thread Siamese connection.
CHAPTER 10 – MEANS OF EGRESS
SECTION 1008
MEANS OF EGRESS ILLUMINATION
Section 1008.3, 3.5 Delete and replace with: 5. Restrooms designed for
simultaneous use by more than one occupant.
(Change: Removed “Public” or “Common Area” to require all multi-occupant
restrooms to require emergency lights)
Section 1008.3.3 Add a new section to read as follows. Additional emergency
lights: Emergency lights may be required at the discretion of the Fire Code
Official for illumination in the event of a power failure.
SECTION 1013
EXIT SIGNS
Section 1013.5 Add a sentence to the end of the section to read as follows: Self-
luminous and Photoluminescent exit signs. Self-luminous and
photoluminescent exit signs are not allowed in place of hardwired, battery
back-up signs.
Section 1013.7 Add a new section to read as follows. Additional Exit Signs: Exit
signs may be required at the discretion of the Fire Code Official to clarify an
exit or exit access.
CHAPTER 11 – CONSTRUCTION REQUIREMENTS FOR EXISTING
BUILDINGS
SECTION 1103
FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
Section 1103.11 Add a new section to read as follows: Existing fire alarm
systems monitoring requirements. Existing fire alarms systems that are
currently not monitored by an approved UL listed Central Station shall become